+ PDF
HC 12 F Local EHT Controller

Description

A load control device intended for automatic and remote discrete control of user power, measuring the current consumed (using external measuring transformers) and voltage on three phases.

The device can be used both independently and as part of automated process supervision and control systems. The product may be installed in outdoor control cabinets.

Data exchange with the monitoring / control system is provided via RS-485/CAN serial interface.

Any setting and modes, and firmware updates are possible via a USB service port.

The device is registered with Russian Instrument Register #67073-17.

P.O. Details

Order Form:

HC-12F конст.png

P.O. Code
Version
HC-12F-D-RC 24 V DC, single integrated RS-485/CAN interface

General Characteristics

                                                                Power Supply

DC supply voltage, V

18...30

Consumed power, W

≤ 4,0

                                                               Control channels

Nr.  

12

Type

Relay, toggle

AC load capacity, A  

0...12

AC switching voltage, V      

0...250

                                                  Current measuring channels

Nr.  

12

Current range, mA     

0...65

Basic percent error referred to full amperage range, %, max

0,5    

Additional percent error of amperage measurements for a 10°C ambient temperature deviation, %, max.

      0,03

Input impedance, Ω (±20 %)

27

Surge protection, V 

up to 30  

Galvanic isolation 

Group

                                                   Voltage measuring channels

Nr. 

3

AC voltage measuring range, V     

0...300

Basic percent error referred to full voltage range, %, max.

1,0    

Additional percent error of voltage measurements for a 10°C ambient temperature deviation, %, max.

0,15

                                               Temperature measuring channel

Sensor wiring diagram 

Three-wire 

Resistance range, Ω 

76.33 to 229.72

For НCХ Pt 100 (α =0.00385 0Cˉ¹) as per GOST 6651

0,5    

Basic percent error referred to full resistance range, %, max     

0,025

Additional percent error of resistance measurements for an 10°C ambient temperature deviation, %, max.

Three-wire

Surge protection, V 

Up to 30  

                                               Discrete input channels 24 V DC

Nr.

28

DC logic low (0), V 

0…5

DC logic high (1), V

15…30

Typical input current @ 24 V (rated), mA

7,7

Galvanic isolation

Group

                                                    Auxiliary control channel

Type       

Relay, NC          

AC load capacity, A         

0...6      

AC switching voltage, V     

0...250

                                                             Communication

Interface

RS-485/CAN      

Communication protocol 

Modbus RTU/CANopen      

Data rate RS-485/CAN, kbps     

4,8...115,2/50...1000

                                        Galvanic isolation (dielectric strength)

Control channels – all other I/O, V

2500

All I/O except for control channels, V

1000

Power input – discrete input channels

No insulation

                                                                Miscellaneous

EMC requirements

Pursuant to GOST 30804.6.2-2013, GOST 30804.6.3-2013

Housing rating

IP30

Dimensions (WxHxD), mm

127,5 х 332,0 х 51,0


Please submit your request