+ PDF
K-PFC УКРМ Cabinet-type capacitors

Description

Cabinet-type capacitors type 6-10 kV K-PFC УКРМ correct power factor, restrict voltage deviations and increase the utilization rate of electrical equipment applied in the power supply systems in industrial plants.

These units may be applied for individual, grouped or centralized power factor correction of time-dependent loads in three-phase 6 kV and 10 kV circuits.

Design

  • A small-size and robust modular design makes it possible to ramp up the system and facilitates transportation, storage, installation and operation.

  • Galvanized cabinets are used indoors and may be equipped with various ventilation systems. Protection rating: IP30 to IP42. Enclosure as per GOST 14693.

  • The design and test methods comply with the latest relevant standards and may be tailored to the Customer’s needs.

  • Simple design and well-proven components ensure high reliability and lower operating expenses.

  • Arc sensors can be used for protection relays.

  • The power factor correction units are factory tested and delivered fully assembled and ready to connect.

  • Power factor correction units type K-PFC consist of a few stages of regulation comprising capacitor units, reactors and switches, all in a single enclosure. Automatic units are capable of modifying the reactive power according to the instant load.

  • Multiple bank regulation based on required power, and system monitoring is performed with a microprocessor-based controller, which additionally issues circuit-related data and generates emergency alarm messages.

General Characteristics

Rated voltage

6.3 to 10.5 kV

Rated frequency

50 Hz

Rated power

50 to 12,000 kVAr

Number of stages of regulation

1 to 14

Short circuit current 

max. 25 kA / 1 sec



Allowable overvoltage (12 hrs per day) 

1.1 х Un

Allowable current overload 

1.3 х In

Types of banks

Fixed rating, fixed rating and a switch, automatic

Capacitor units

Plastic film, ecofriendly liquid dielectric

Connection

- capacitor banks with single-phase capacitor units connected via wye or double wye are rated at 12000 kVAr max., operating voltage 10 kV max.

- three-phase module banks connected via wye are rated at 4,800 kVAr max., operating voltage 7.2 kV max.

Dischargers

Resistors integrated into capacitor units to discharge to 75 V in 10 minutes

Reactors

Air-core current limiting reactors or core filter reactors

Switch control for regulation

Switch control for regulation

Switches  

Vacuum (SF6) contactors or breakers

Installation  

Indoors

Elevation above sea level 

< 1000 m (or higher, upon request)

Enclosure protection rating

IP30 to IP42

Material

Galvanized steel

Cooling method 

Natural air cooling, fan ventilated with thermal switch or via a heat exchanger

Cable entry 

Top, bottom or side

Door locking 

Manual without a lock, key lock, block-out electric lock or special safety lock

Condensate protection 

Heater with thermal switch

Lighting

Fluorescent switch light

Operating temperature 

25°C negative to 50°C positive

- average (24 hours): + 35°C

- average (1 year): + 25°C

Storage temperature 

50°C negative to 55°C positive

Transportation temperature 

50°C negative to 70°C positive

Relative humidity 

25% to 90% (without moisture condensation)

Testing

Validation and type tests of 100% components. Functional and electrical testing of capacitor banks. Any extra testing as agreed.