CK-MI-1M Open Platform Cable Heat Tracing
Description
A CK-MI-1M mineral-insulated constant wattage heating element is used for freezing protection or to maintain material temperature in the pipelines, vessels and equipment for exposure to temperatures below 850°C.
A mineral-insulated constant wattage heating element is supplied as a kit consisting of a heat trace cable, cold tails, a connection kit and cold lead cables.
Design
Heating element is sized to the Customer’s specifications. The scope of supply includes a made-to-order heat cable, with a brazed cold lead connector and a cold lead cable for junction box connection, and properly sized brass glands. A gland is used to connect the cable into the power box while ensuring adequate tightness for hazardous area applications.
P.O. Details
E.g., a P.O. for a CK-MI.1M type heating element with a heat trace cable, stainless steel jacketed, resistivity = 2500 Ω/km and design length = 54 m, @ 230 V operating voltage, 2.5 sq.mm and 1.5 m long cold tail, should contain the following number: CK-MI-1M.S/2500/54/230/CL2.5-1.5
General Characteristics
Max exposure temperature for an alloy 400 jacketed cable |
400 °С |
Max exposure temperature for an alloy 825 jacketed cable |
700 °С |
Max exposure temperature for a stainless steel jacketed cable |
700 °С |
Max exposure temperature for an alloy 600 jacketed cable |
850 °С |
Max maintenance temperature |
Alloy 400 - 380 °С
Stainless steel - 670 °С
Alloy 600 - 700 °С Alloy 825 - 670 °С |
Supply voltage |
600 V max |
Сonnection |
230 V - 1P, 380 V - 2P, 380 V - 3P (wye) |
Jacket material |
Alloy 825, Alloy 600, Alloy 400, Stainless Steel |
Wire material |
Cu, Ni-Cr, Cu-Ni alloy |
Type of heat cable |
Series type, constant wattage |
Hazardous area classification |
Hazardous, normal |
Certificate, Ex protection |
Pursuant to CU TR 012/2011, # RU C-RU. НА65.В.00705/20, 1Ex de IIC T6...T1 Gb X, 1Ex e IIC T6...T1 Gb X, Ex tb IIIC Т85°С...Т450°С Db X |
Modifications
A CK-MI-1M parallel type constant wattage heating element is produced in several designs based on heat cables with different jackets. Jacketing material is consistent with marking
Alloy 400...............................................................................................................CK-MI-1M.N
Stainless steel......................................................................................................CK-MI-1M.S
Alloy 600...............................................................................................................CK-MI-1M.I
Alloy 825...............................................................................................................CK-MI-1M.A