CK-MI-2M Metal-Jacketed Constant Wattage Heating Element
Description
A CK-MI-1M mineral-insulated constant wattage heating element is used for freezing protection or to maintain material temperature in the pipelines, vessels and equipment for exposure to temperatures below 425°C.
A mineral-insulated constant wattage heating element is supplied as a kit consisting of a heat trace cable, cold tails, a connection kit and cold lead cables.
Design
Metal-jacketed constant wattage heating element CK-MI-2M is used for freezing protection or to maintain material temperature in the pipelines, vessels and equipment for exposure to temperatures below 425 °С.
Metal-jacketed constant wattage heating element is supplied as a kit consisting of a heat trace cable, cold gland, and end termination. As this is a parallel-type cable with a segmental heater, cold entry requires cable end fan-out for termination.
P.O. Details
To place a P.O., please select the item number of the heating element from the Marking table that suits your project specification, and specify the design length (m). E.g., a P.O. for a CK-MI-2M type heating element with a heat trace cable, specific output = 70 W/m and design length = 30 m, should contain the following number: CK-MI-2M.70/30
General Characteristics
Max exposure temperature |
425 °С |
Max maintenance temperature |
340 °С |
Supply voltage |
~230 V |
Jacket material |
Al |
Wire material |
Cu, Cu-Ni alloy / Alloy 600 |
Type of heat cable |
Parallel, segmented, constant wattage |
Hazardous area classification |
Hazardous, normal |
Certificate, Ex protection |
Pursuant to CU TR 012/2011, # RU C-RU. НА65.В.00705/20, 1Ex e IIC T6...T1 Gb X, Ex tb IIIC T85°С...T450°С Db X |
Marking
CK-MI-2M.15 |
15 W/m |
CK-MI-2M.30 |
30 W/m |
CK-MI-2M.50 |
50 W/m |
CK-MI-2M.70 |
70 W/m |
CK-MI-2M.100 |
100 W/m |
CK-MI-2M.150 |
150 W/m |