+ PDF
K-PANEL

Description

Low-voltage package systems of K-PANEL series are intended to receive and distribute three-phase AC, 50 Hz, 0.4 kV and 0.69 kV electrical power in dead-earthed or insulated neutral, electrical equipment control and fault current / overload protection systems.

Design

  • Top or backside location of main distribution busbars.

  • All K-PANEL equipment may have either a fixed or pluggable configuration. Plug-in design is achieved by using ready-to-use typical pluggable modules (K-MODE).
  • K-PANEL panels have max. IP54 rating.
  • K-PANEL panels may be sectioned to 4b to ensure safe operation.
  • The colour of K-PANEL depends on the Customer’s preferences.
  • Max main busbar current is 3,200 A.

P.O. Details

A draw-out distribution and control board is fabricated based on data sheets and specifications.

General Characteristics

Rated insulation voltage

1000 V

Rated voltage 

400 V

Frequency

50 Hz

Rated impulse withstand voltage

12 kV

Rated secondary voltage, V   

12/24/48/230

Overvoltage category   

IV

Current rating (max) In

3200 A

Rated short-time withstand current Icw

85 kA (rms value) / 1 sec

Peak withstand rating Ipk

187 kА

Earthing system 

TT, IT, TN-C, TN-C-S, TN-S

Certificate, Ex protection

Meets CU TR 004/2011, CU TR 020/2011, # ЕАЭС RU C-RU.МЮ62.В.01286/19


Please submit your request